Environment
Conditions
Storage
temperature
-40°C
–+70°C, and the temperature changing rate is less than
1°C/minute.
Running
environment
condition
The installation site should meet the following requirements.
Away from electromagnetic radiation sources.
Away from oil mist, corrosive gases and combustible gases.
Ensure foreign object like metal powder, dust, oil and water will not
fall into the VFD (do not install the VFD onto combustible object like
wood).
Away from radioactive substance and combustible objects.
Away from harmful gases and liquids.
Low salt content.
No direct sunlight.
Altitude
Below 1000m.
When the altitude exceeds 1000m, derate by 1% for every increase
of 100m.
When the altitude exceeds 3000m, consult the local INVT dealer or
office for details.
Vibration
Max. vibration acceleration: 5.8m/s
2
(0.6g)
Installation
direction
The VFD should be installed on an upright position to ensure sufficient
cooling effect.
Note:
Goodrive20-UL series VFDs should be installed in a clean and ventilated environment
according to enclosure classification.
Cooling air must be clean, free from corrosive materials and electrically conductive dust.
3.1.2 Installation direction
The VFD may be installed in a cabinet.
The VFD needs be installed in the vertical position. Check the installation site according to the
requirements below.
Refer to Appendix B "Dimension drawings" in the appendix for frame
details.
3.1.3 Installation mode
The VFD can be installed in two different ways, depending on the frame size:
a) Wall mounting (for all frame sizes)
b) Rail mounting (for all frame sizes, but need optional installation bracket)