Goodrive20-UL Series VFD
Function parameters
-48-
Function
code
Name
Description
Default Modify
P03.24
Max.
voltage limit
P03.24 set the Max. Voltage of the VFD, which
is dependent on the site situation.
Setting range: 0.0
–120.0%
100.0%
◎
P03.25
Pre-exciting
time
Pre-activate the motor when the VFD starts up.
Build up a magnetic field inside the VFD to
improve the torque performance during the
starting process.
Setting time: 0.000
–10.000s
0.300s
○
P03.26
Weakenin
g
proportion
al gain
0
–8000
1200
○
P03.27
Speed
display
selection
of vector
control
0: Display at the actual value
1: Display at the setting value
0
○
P04 group SVPWM control
Function
code
Name
Description
Default Modify
P04.00
V/F curve
setting
These function codes define the V/F curve of
Goodrive20-UL motor 1 to meet the need of
different loads.
0: Straight line V/F curve; applying to the
constant torque load
1: Multi-dots V/F curve
2: 1.3th power low torque V/F curve
3: 1.7th power low torque V/F curve
4: 2.0th power low torque V/F curve
Curves 2
–4 apply to the torque loads such as
fans and water pumps. Users can adjust
according to the features of the loads to get the
best performance.
5: Customized V/F (V/F separation); in this
mode, V can be separated from f and f can be
adjusted through the frequency reference
channel set by P00.06 or the voltage reference
channel set by P04.27 to change the feature of
0
◎