Goodrive20-UL Series VFD
Communication protocol
-119-
if(crc_value&0x0001)crc_value=(crc_value>>1)^0xa001;
else crc_value=crc_value>>1;
} }
return(crc_value);
}
In ladder logic, CKSM calculated the CRC value according to the frame with the table inquiry.
The method is advanced with easy program and quick calculation speed. But the ROM space
the program occupied is huge. So use it with caution according to the program required space.
7.3 RTU command code and communication data
7.3.1 Command code 03H
03H (correspond to binary 0000 0011), reading N words (continuously up to 16 words)
Command code 03H means that if the master read data from the VFD, the reading number
depends on the "data number" in the command code. The Max. Continuous reading number is
16 and the parameter address should be continuous. The byte length of every data is 2 (one
word). The following command format is illustrated by hex (a number with "H" means hex) and
one hex occupies one byte.
The command code is used to read the working stage of the VFD.
For example, read continuous 2 data content from0004H from the VFD with the address of
01H (read the content of data address of 0004H and 0005H), the frame structure is as below:
RTU master command message (from the master to the VFD)
START
T1-T2-T3-T4
ADDR
01H
CMD
03H
High bit of the start address
00H
Low bit of the start address
04H
High bit of data number
00H
Low bit of data number
02H
CRC low bit
85H
CRC high bit
CAH
END
T1-T2-T3-T4
T1-T2-T3-T4 between START and END is to provide at least the time of 3.5 bytes as the
leisure time and distinguish two messages for the avoidance of taking two messages as one
message.