P01.03
Braking
current
before
starting
The VFD will carry out DC braking at the braking
current set before starting and it will speed up
after the DC braking time. If the DC braking time
is set to 0, the DC braking is invalid.
The stronger the braking current, the bigger the
braking power. The DC braking current before
starting is the percentage of rated current of the
VFD.
Setting range of P01.03: 0.0
–100.0% (rated
current peak of the VFD)
Setting range of P01.04: 0.00
–50.00s
0.0%
◎
P01.04
Braking
time
before
starting
0.00s
◎
P01.05
ACC/DEC
selection
The changing mode of the frequency during
start-up and running. (t1=P01.06, t2=P01.07)
0: Linear type
The output frequency increases or decreases
linearly.
fmax
Output frequency
t1
t2
T
1: S curve, the output frequency will increase or
decrease according to the S curve.
2
Output frequency
T
S curve is generally used in cases where
smooth start/stop is required, eg, elevator,
conveyer belt, etc.