Goodrive20-UL Series VFD
Function parameters
-75-
Function
code
Name
Description
Default Modify
Y1
RO1, RO2
S terminal
/HDI
Reach the set
counting value
Reach the designated
counting value
Setting range of P08.25: P08.26
–65535
Setting range of P08.26: 0
–P08.25
P08.27
Setting
running
time
Pre-set running time of the VFD. When the
accumulative running time achieves the set
time, the multi-function digital output terminals
will output the signal of "running time arrival".
Setting range: 0
–65535min
0m
○
P08.28
Time of
fault reset
The time of the fault reset: set the fault reset
time by selecting this function. If the reset time
exceeds this set value, the VFD will stop for the
fault and wait to be repaired.
The interval time of the fault reset: The interval
between the time when the fault occurs and the
time when the reset action occurs.
Setting range of P08.28: 0
–10
Setting range of P08.29: 0.1
–100.0s
0
○
P08.29
Interval
time of
automatic
fault reset
1.0s
○
P08.30
Frequency
decreasing
ratio in
drop
control
The output frequency of the VFD changes as
the load. And it is mainly used to balance the
power when several VFDs drive one load.
Setting range: 0.00
–50.00Hz
0.00Hz
○
P08.32
FDT1
electrical
level
detection
value
When the output frequency exceeds the
corresponding frequency of FDT electrical level,
the multi-function digital output terminals will
output the signal of "frequency level detect FDT"
until the output frequency decreases to a value
lower than (FDT electrical level
—FDT retention
detection value) the corresponding frequency,
the signal is invalid. Below is the waveform
diagram:
60.00Hz
○
P08.33
FDT1
retention
detection
value
5.0%
○
P08.34
FDT2
electrical
level
detection
value
60.00Hz
○