Goodrive20-UL Series VFD
Function parameters
-45-
Function
code
Name
Description
Default Modify
0.000
–10.000s
Setting range of P03.02: 0.00Hz
–P00.05
Setting range of P03.05: P03.02
–P00.03
P03.06
Speed loop
output filter
0
–8 (corresponds to 0–2
8
/10ms)
0
○
P03.07
Compensat
ion
coefficient
of vector
control
electromoti
on slip
Slip compensation coefficient is used to adjust
the slip frequency of the vector control and
improve the speed control accuracy of the
system. Adjusting the parameter properly can
control the speed steady-state error.
Setting range: 50%
–200%
100%
○
P03.08
Compensat
ion
coefficient
of vector
control
brake slip
100%
○
P03.09
Current
loop
percentage
coefficient
P
Note
:
The two function codes impact the dynamic
response speed and control accuracy of the
system. Generally, you do not need to
modify the two function codes.
The parameters P03.09 and P03.10 are
applicable only to SVC 0 (P00.00=0).
Setting range: 0
–65535
1000
○
P03.10
Current
loop
integral
coefficient I
1000
○
P03.11
Torque
setting
method
This parameter is used to enable the torque
control mode, and set the torque setting
means.
0: Torque control is invalid
1: Keypad setting torque (P03.12)
2: Analog AI1 setting torque
3: Analog AI2 setting torque
4: Analog AI3 setting torque
5: Pulse frequency HDI setting torque
6: Multi-step torque setting
7: Modbus communication setting torque
8
–10: Reserved
0
○