Goodrive20-UL Series VFD
Function parameters
-37-
Function
code
Name
Description
Default Modify
P01.06
ACC time
of the
starting
step of S
curve
Setting range: 0.0
–50.0s
Note:
Valid when P01.05 is 1.
0.1s
◎
P01.07
DEC time
of the
ending
step of S
curve
0.1s
◎
P01.08
Stop
selection
0: Decelerate to stop: after the stop command
becomes valid, the VFD decelerates to reduce
the output frequency during the set time. When
the frequency decreases to 0Hz, the VFD stops.
1: Coast to stop: after the stop command
becomes valid, the VFD ceases the output
immediately. And the load coasts to stop at the
mechanical inertia.
0
○
P01.09
Starting
frequency
of DC
braking
Starting frequency of DC braking: start the DC
braking when running frequency reaches
starting frequency determined by P1.09.
Waiting time before DC braking: VFDs blocks
the output before starting the DC braking. After
this waiting time, the DC braking will be started
so as to prevent over-current fault caused by
DC braking at high speed.
DC braking current: the value of P01.11 is the
percentage of rated current of VFD. The bigger
the DC braking current is, the greater the
braking torque is.
DC braking time: the retention time of DC
braking. If the time is 0, the DC braking is
invalid. The VFD will stop at the mode of
coasting to stop.
0.00Hz
○
P01.10
Waiting
time
before DC
braking
0.00s
○
P01.11
DC
braking
current
0.0%
○
P01.12
DC
braking
time
0.00s
○