Goodrive20-UL Series VFD
Function parameters
-83-
Function
code
Name
Description
Default Modify
P09.08
PID control
deviation
limit
The output of PID system is relative to the
maximum deviation of the close loop reference.
As shown in the diagram below, PID adjustor
stops to work during the deviation limit. Set the
function properly to adjust the accuracy and
stability of the system.
Output frequency
T
T
Feedback value
Bias limit
Reference
value
Setting range: 0.0
–100.0%
0.0%
○
P09.09
Output
upper limit
of PID
These parameters are used to set the upper
and lower limit of the PID adjustor output.
100.0 % corresponds to Max. Frequency or the
Max. Voltage of ( P04.31)
Setting range of P09.09: P09.10
–100.0%
Setting range of P09.10: -100.0%
–P09.09
100.0%
○
P09.10
Output
lower limit
of PID
0.0%
○
P09.11
Feedback
offline
detection
value
Set the PID feedback offline detection value,
when the detection value is smaller than or
equal to the feedback offline detection value,
and the lasting time exceeds the set value in
P09.12, the VFD will report "PID feedback
offline fault" and the keypad will display PIDE.
T
Output frequency
t1
t2
P09.11
t1<t2, so the VFD
continues to work
t2=P09.12
In running
Fault output PIDE
PIDE
Setting range of P09.11: 0.0
–100.0%
Setting range of P09.12: 0.0
–3600.0s
0.0%
○
P09.12
Feedback
offline
detection
time
1.0s
○
P09.13
PID
adjustment
selection
0x00
–0x11
Ones place:
0: Keep on integral adjustment when the
0x0001
○
Содержание GD20-0R4G-2-UL