Goodrive20-UL Series VFD
Function parameters
-28-
Function
code
Name
Description
Default Modify
1 is suitable in high performance cases with the
advantage of high accuracy of rotating speed
and torque. It does not need to install pulse
encoder.
2: SVPWM control
2 is suitable in applications which do not need
high control accuracy, such as the load of fan
and pump. One VFD can drive multiple motors.
P00.01
Run
command
channel
Select the run command channel of the VFD.
The control command of the VFD includes: start,
stop, forward/reverse rotating, jogging and fault
reset.
0:
Keypad
running
command
channel
("LOCAL/REMOT" light off)
Carry out the command control by RUN,
STOP/RST on the keypad.
Set the multi-function key QUICK/JOG to
FWD/REVC shifting function (P07.02=3) to
change the running direction; press
RUN
and
STOP/RST
simultaneously in running state to
make the VFD coast to stop.
1:
Terminal
running
command
channel
("LOCAL/REMOT" flickering)
Carry out the running command control by the
forward rotation, reverse rotation and forward
jogging and reverse jogging of the multi-function
terminals
2: Communication running command channel
("LOCAL/REMOT" on);
The running command is controlled by the
upper monitor via communication
0
○
P00.03
Max.
output
frequency
The parameter is used to set the max. output
frequency of the VFD. It is the basis of
frequency setup and the
acceleration/deceleration.
Setting range: P00.04
–400.00Hz
60.00Hz
◎