Goodrive20-UL Series VFD
Fault tracking
-108-
Fault
code
Fault type
Possible cause
Solutions
UV
[10] Bus
undervoltage
The voltage of the
power supply is too
low.
The overvoltage stall
protection is not open.
Check the input power
of the supply line.
Check the setting of
relative function
codes.
OL1
[11] Motor overload
The voltage of the
power supply is too
low.
The motor setting
rated current is
incorrect.
The motor stall or load
transients is too
strong.
Check the power of
the supply line
Reset the rated
current of the motor
Check the load and
adjust the torque lift
OL2
[12] VFD overload
The acceleration is
too fast.
Reset the rotating
motor.
The voltage of the
power supply is too
low.
The load is too heavy.
Close loop vector
control, reverse
direction of the code
panel and long
low-speed operation.
Increase the ACC
time
Avoid the restarting
after stopping.
Check the power of
the supply line
Select a VFD with
bigger power.
Select a proper motor.
SPI
[13] Phase loss on
input side
Phase loss or
fluctuation of input
R,S,T
Check input power
Check installation
distribution.
SPO
[14] Phase loss on
output side
U,V,W phase loss
input (or serious
asymmetrical three
phase of the load)
Check the output
distribution.
Check the motor and
cable.