Goodrive20-UL Series VFD
Function parameters
-33-
Function
code
Name
Description
Default Modify
P00.14
Carrier
frequency
setting
Carrier
frequency
Electromagnetic
noise
Noise and leakage
current
Heating
eliminating
High
Low
High
Low
High
Low
1kHz
10kHz
15kHz
The relationship table of the motor type and
carrier frequency:
Motor type
Factory setting of
carrier frequency
0.4
–2.2kW
8kHz
The advantage of high carrier frequency: ideal
current waveform, little current harmonic wave
and motor noise.
The disadvantage of high carrier frequency:
increasing the switch loss, increasing VFD
temperature and the impact to the output
capacity. The VFD needs to derate on high
carrier frequency. At the same time, the leakage
and
electrical
magnetic
interference
will
increase.
Applying low carrier frequency is contrary to the
above, too low carrier frequency will cause
unstable running, torque decreasing and surge.
The manufacturer has set a reasonable carrier
frequency when the VFD is in factory. In
general, users do not need to change the
parameter.
When the frequency used exceeds the default
carrier frequency, the VFD needs to derate 20%
for each additional 1k carrier frequency.
Setting range: 1.0
–15.0kHz
Depend
on model
○
P00.15
Motor
parameter
autotunin
g
0: No operation
1: Rotation autotuning
Comprehensive motor parameter autotune
It is recommended to use rotation autotuning
0
◎