Goodrive20-UL Series VFD
Function parameters
-94-
Function
code
Name
Description
Default Modify
0: Disable
1: Enable
Tens place: Second ACC/DEC time
selection
0: Disable
1: Enable. When the running frequency
exceeds P08.36, ACC/DEC time is switched
to the second ACC/DEC time.
P13 group SM control
Function
code
Name
Description
Default Modify
P13.09
Frequency
switching
point
0.00
–630.00
50.00
○
P13.13
Braking
current of
short circuit
After the VFD starts, when P01.00=0, set
P13.14 to non-zero value and begin short
circuit braking.
After the VFD stops, when the operation
frequency is less than P01.09, set P13.15 to
non-zero value and begin stopping
short-circuit braking and then DC braking.
Setting range of P13.13: 0.0
–150.0%
(relative to the percentage of rated current of
the VFD)
Setting range of P13.14: 0.00
–50.00s
0.0%
○
P13.14
Braking
retention
time of
starting
short circuit
0.00s
○
P13.15
Braking
retention
time of
stopping
short circuit
0.00s
○
P14 group Serial communication
Function
code
Name
Description
Default Modify
P14.00
Local
communicati
on address
Setting range: 1
–247
When the master is writing the frame, the
communication address of the slave is set to
0. The broadcast address is the
communication address. All slaves on the
Modbus fieldbus can receive the frame, but
the salve doesn't answer.
1
○