Goodrive20-UL Series VFD
Function parameters
-74-
Function
code
Name
Description
Default Modify
Setting range of P08.15: 0.0
–100.0% (relative to
the set frequency)
Setting range of P08.16: 0.0
–50.0% (relative to
the traverse range)
Setting range of P08.17: 0.1
–3600.0s
Setting range of P08.18: 0.1
–3600.0s
P08.20
Analog
calibration
function
selection
0: Invalid
1: Valid
1
◎
P08.21
DEC time
of
emergency
stop
0.0
–6553.5 s
0.0 indicates coast to stop
0.0 s
○
P08.22
Delay to
enter the
sleep state
0.0
–3600.0s
It indicates the delay to enter the sleep state,
and it is valid only when ones place of P01.19 is
set to 2.
2.0s
○
P08.24
Energy
braking for
stop
0: Disable
1: Enable
1
○
P08.25
Set count
value
The counter works by the input terminal signals
of S terminal (set as "Counter trigger") or HDI
(set P05.00 to 1).
When the count value reaches the specified
number, the multi-function output terminal
sends the signal of "The specified count value is
reached" and the counter continues to count;
when the count value reaches the set number,
the multi-function output terminal sends the
signal of "The set count value is reached", and
the counter will be reset to zero and recount
when the next pulse occurs.
The value of P08.26 cannot be greater than that
of P08.25.
The function is illustrated as below:
0
○
P08.26
Specified
count
value
0
○