Goodrive20-UL Series VFD
Function parameters
-54-
Function
code
Name
Description
Default Modify
P05.10
Polarity
selection
of the input
terminals
The function code is used to set the polarity of
the input terminals.
Set the bit to 0, the input terminal is anode.
Set the bit to 1, the input terminal is cathode.
BIT8
BIT7
BIT6
BIT5
BIT4
HDI
S8
S7
S6
S5
BIT3
BIT2
BIT1
BIT0
S4
S3
S2
S1
Setting range: 0x000
–0x1FF
0x000
○
P05.11
Switch
filter time
Set the sample filter time of S1
–S4 and HDI
terminals. If the interference is strong, increase
the parameter to avoid wrong operation.
0.000
–1.000s
0.010s
○
P05.12
Virtual
terminals
setting
0x000
–0x1FF (0: Disabled, 1:Enabled )
BIT0: S1 virtual terminal
BIT1: S2 virtual terminal
BIT2: S3 virtual terminal
BIT3: S4 virtual terminal
BIT4: S5 virtual terminal
BIT5: S6 virtual terminal
BIT6: S7 virtual terminal
BIT7: S8 virtual terminal
BIT8: HDI virtual terminal
Note:
After a virtual terminal is enabled, the
state of the terminal can be changed only in
communication mode. The communication
address is 0x200A.
0x000
◎
P05.13
Terminals
control
running
mode
Set the operation mode of the terminals control
0: 2-wire control 1, comply the enable with the
direction. This mode is widely used. It
determines the rotation direction by the defined
FWD and REV terminals command.
FWD
REV
COM
K1
K2
Running
command
FWD
REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Stopping
Hold on
Forward
running
Reverse
running
0
◎