Goodrive20-UL Series VFD
Function parameters
-52-
Function
code
Name
Description
Default Modify
Vmax
Vmin
Vset
t1
t2
Time
t1=P04.29
t2=P04.30
P04.33
Weakeni
ng
coefficien
t in
constant
power
zone
Adjust the output voltage of the VFD in SVPWM
mode when weakening.
Note:
Invalid in the constant torque mode.
Output Voltage
Output frequency
V
out
V
b
f
b
2f
b
(P04.33-1.00) x V
b
Setting range of P04.33: 1.00
–1.30
1.00
○
P05 group Input terminals
Function
code
Name
Description
Default Modify
P05.00
HDI input
selection
0: HDI is high pulse input. See P05.50
–P05.54
1: HDI is switch input
0
◎
P05.01
S1
terminals
function
selection
Note
: S1
–S4, HDI are the upper terminals on
the control board and P05.12 can be used to set
the function of S5
–S8
0: No function
1: Forward rotation operation
2: Reverse rotation operation
3: 3-wire control operation
4: Forward jogging
5: Reverse jogging
6: Coast to stop
7: Fault reset
8: Operation pause
9: External fault input
10: Increasing frequency setting (UP)
11: Decreasing frequency setting (DOWN)
12: Cancel the frequency change setting
1
◎
P05.02
S2
terminals
function
selection
4
◎
P05.03
S3
terminals
function
selection
7
◎
P05.04
S4
terminals
function
selection
0
◎