Goodrive20-UL Series VFD
Communication protocol
-126-
Function
Address
Data description
R/W
characteristics
Bit5: =1 DC braking =0: DC
braking prohibition
200AH
Virtual input terminal command, range:
0x000
–0x1FF
R/W
200BH
Virtual output terminal command, range:
0x00
–0x0F
R/W
200CH
Voltage setting value (special for V/F
separation)
(0
–1000, 1000 corresponds to the
100.0% of the rated voltage of the motor)
R/W
200DH
AO output setting 1
(-1000
–1000, 1000 corresponds to
100.0%)
R/W
200EH
AO output setting 2
(-1000
–1000, 1000 corresponds to
100.0%)
R/W
SW 1 of the VFD
2100H
0001H: Forward running
R
0002H: Forward running
0003H: Stop
0004H: Fault
0005H: POFF state
0006H: Pre-exciting state
SW 1 of the VFD
2101H
Bit0: =0: bus voltage is not established
=1: bus voltage is established
Bit1
–2: =00: motor 1 =01: motor 2
=10: motor 3 =11: motor 4
Bit3: =0: asynchronous motor
=1: synchronous motor
Bit4: =0: pre-alarm without overload
=1: overload pre-alarm
Bit5
–
Bit6: =00: keypad control
=01: terminal control
=10: communication control
R
Fault code of the
VFD
2102H
See the fault type instruction
R
Identifying code
of the VFD
2103H
GD20-UL-----0x0106
R
Operation
frequency
3000H
0
–Fmax, unit: 0.01Hz
Compatible with
the
R