Goodrive20-UL Series VFD
Function parameters
-29-
Function
code
Name
Description
Default Modify
P00.04
Upper
limit of the
running
frequency
The upper limit of the running frequency is the
upper limit of the output frequency of the VFD
which is lower than or equal to the maximum
frequency.
Setting range: P00.05
–P00.03 (Max. output
frequency)
60.00Hz
◎
P00.05
Lower
limit of the
running
frequency
The lower limit of the running frequency is that
of the output frequency of the VFD.
The VFD runs at the lower limit frequency if the
set frequency is lower than the lower limit.
Note:
Max. output frequency ≥ Upper limit
frequency ≥ Lower limit frequency
Setting range: 0.00Hz
–P00.04 (Upper limit of
the running frequency)
0.00Hz
◎
P00.06
A
frequency
command
selection
0: Keypad data setting
Modify the value of function code P00.10 (set
the frequency by keypad) to modify the
frequency by the keypad.
1: Analog AI1 setting (corresponding keypad
potentiometer)
2: Analog AI2 setting (corresponding terminal
AI2)
3: Analog AI3 setting (corresponding terminal
AI3)
Set the frequency by analog input terminals.
Goodrive20-UL series VFDs provide 3 channels
analog input terminals as the standard
configuration, of which AI1 is adjusting through
analog
potentiometer,
while
AI2
is
the
voltage/current option (0
–10V/0–20mA) which
can be shifted by jumpers; while AI3 is voltage
input (-10V
–+10V).
Note:
When analog AI2 select 0
–20mA input,
the corresponding voltage of 20mA is 10V.
100.0% of the analog input setting corresponds
to the maximum frequency (function code
P00.03) in forward direction and -100.0%
corresponds to the maximum frequency in
0
○
P00.07
B
frequency
command
selection
2
○