Goodrive20-UL Series VFD
Function parameters
-56-
Function
code
Name
Description
Default Modify
COM
SB3
SB2
SB1
FWD
REV
SIn
Sln
FWD
REV
Directio
n
ON
OFF→
ON
ON
Forward
OFF
Reverse
ON
ON
OFF→ON
Forward
OFF
Reverse
ON→
OFF
Decelerat
e to stop
Note
: For the 2-wire running mode, when
FWD/REV terminal is valid, the VFD stop
because of the stopping command from other
sources, even the control terminal FWD/REV
keeps valid; the VFD won't work when the
stopping command is canceled. Only when
FWD/REV is relaunched, the VFD can start
again. For example, the valid STOP/RST stop
when PLC signal cycles stop, fixed-length stop
and terminal control (see P07.04).
P05.14
S1
terminal
switching
on delay
time
The function code defines the corresponding
delay
time
of
electrical
level
of
the
programmable terminals from switching on to
switching off.
Si electrical level
Si valid
Invalid
Invalid
Switch-on
delay
Switch-off
delay
Valid
Setting range: 0.000
–50.000s
0.000s
○
P05.15
S1
terminal
switching
off delay
time
0.000s
○