Goodrive20-UL Series VFD
Optional peripheral accessories
-145-
The model GD20-2R2G-S2-UL uses terminal blocks of DEGSON, and the tightening torque
must be 4.4 in-lb or equivalent.
The models GD20-0R4G-2-UL/GD20-0R7G-2-UL/GD20-0R7G-4-UL/GD20-1R5G-4-UL/
GD20-2R2G-4-UL use terminal blocks of SUCCEED, and the tightening torque must be 7 in-lb
or equivalent.
Tightening torque and wire range for field grounding wiring terminals are marked adjacent to
the terminal or on the wiring diagram.
Model No.
Required Torque
(in-lbs)
Wire Range (AWG)
GD20-0R4G-S12
10
12
GD20-0R7G-S12
GD20-1R1G-S12
GD20-0R4G-S2-UL
10
14
GD20-0R7G-S2-UL
10
12
GD20-1R5G-S2-UL
10
12
GD20-2R2G-S2-UL
10
10
GD20-0R4G-2-UL
10
14
GD20-0R7G-2-UL
GD20-0R7G-4-UL
GD20-1R5G-4-UL
GD20-2R2G-4-UL
C.3.2 Control cables
All analog control cables and the cable used for the frequency input must be shielded.
The relay cable needs the cable type with braided metallic screen.
Note:
Run analog and digital signals in separate cables.
C.4 Fuse
It is necessary to add fuse for the avoidance of overload.
It is appropriate to use a breaker (MCCB) which complies with the VFD power in the 3-phase
AC power and input power and terminals. The capacity of the VFD should be 1.5-2 times of
the rated current.
Due to the inherent operating principle and construction of circuit
breakers, independent of the manufacturer, hot ionized gases may
escape from the breaker enclosure in case of a short-circuit. To ensure
safe use, special attention must be paid to the installation and placement
of the breakers. Follow the manufacturer's instructions.