Goodrive20-UL Series VFD
Function parameters
-65-
Function
code
Name
Description
Default Modify
2: Lock part of the keys (lock PRG/ESC key
only)
P07.03
QUICK/JO
G the
shifting
sequence
of running
command
When P07.02=6, set the shifting sequence of
running command channels.
0:
Keypad control→terminals control
→communication control
1:
Keypad control←→terminals control
2:
Keypad control←→communication control
3:
Terminals control←→communication control
0
○
P07.04
STOP/RS
T stop
function
Select the stop function by STOP/RST.
STOP/RST is effective in any state for the
keypad reset.
0: Only valid for the keypad control
1: Both valid for keypad and terminals control
2: Both valid for keypad and communication
control
3: Valid for all control modes
0
○
P07.05
Displayed
parameter
s 1 of
running
state
0x0000
–0xFFFF
BIT0: Running frequency (Hz on)
BIT1: Set frequency (Hz flickering)
BIT2: Bus voltage (V on)
BIT3: Output voltage (V on)
BIT4: Output current (A on)
BIT5: Running rotation speed (rpm on)
BIT6: Output power (% on)
BIT7: Output torque (% on)
BIT8: PID reference (% flickering)
BIT9: PID feedback value (% on)
BIT10: Input terminals state
BIT11: Output terminals state
BIT12: Torque set value (% on)
BIT13: Pulse counter value
BIT14: Reserved
BIT15: PLC and the current step of multi-step
speed
0x03FF
○
P07.06
Displayed
parameter
s 2 of
0x0000
–0xFFFF
BIT0: Analog AI1 value (V on)
BIT1: Analog AI2 value (V on)
0x0000