Electrical Maintenance
Unit Wiring
Inspect unit wiring, wire harnesses, and the controller during pre-trip inspection and every 1,000
operating hours to protect against unit malfunctions due to open or short circuits. Look for loose, chaffed
or broken wires on the unit; open or short circuits and damaged components on the controller printed
circuit board.
Inspect electrical contactor points for pitting or corrosion every 1,000 operating hours. Repair or replace
as necessary.
High Pressure Cutout Switch
A high pressure cutout switch is located on the compressor discharge service manifold of each
compressor. If a high pressure cutout switch is suspected of being defective, replace it with a known good
switch.
R-23 High Pressure Cutout Switch
If the R-23 compressor discharge pressure rises above 3250 ± 50 kPa, 32.5 ± 0.5 bar, 470 ± 7 psig, the
high pressure cutout opens to interrupt the ground circuit to the compressor contactor:
•
R-23 compressor STOPS immediately.
•
LCD Display Message: No response to R-23 high pressure cutout.
•
Evaporator and condenser fans and R-134a compressor continue normal operation.
•
R-23 compressor will restart when the overload condition is corrected (switch closes) as long as
power is available. The high pressure switch resets (closes) when the pressure drops to 2590 ± 250
kPa, 25.9 ± 2.5 bar, 375 ± 38 psig.
R-134a High Pressure Cutout Switch
If the R-134a compressor discharge pressure rises above 2410 ± 68 kPa, 24.1 ± 0.68 bar, 350 ± 10 psig,
the high pressure cutout opens to interrupt the ground circuit to the compressor contactor:
•
R-134a compressor STOPS immediately.
•
LCD Display Message: R-134a high pressure cutout feedback missing.
•
Evaporator and condenser fans continue normal operation.
•
R-23 compressor stops.
•
R-134a compressor will restart when the overload condition is corrected (switch closes) as long as
power is available. The high pressure switch resets (closes) when the pressure drops to 1640 ± 68 kPa,
16.4 ± 0.68 bar, 238 ± 10 psig.
•
R-23 compressor will restart 30 seconds after R-134a compressor restarts.
Condenser Fan and Evaporator Fan Rotation
NOTE: If both the condenser fan and evaporator fans are rotating backwards, diagnose the automatic
phase selection system for Alarm Code 18.
Содержание Thermo King CRR DF MPC2000
Страница 5: ...4 ...
Страница 11: ...List of Figures 10 ...
Страница 13: ...Introduction 12 ...
Страница 19: ...Safety Precautions 18 ...
Страница 21: ...Service Guide 20 ...
Страница 47: ...Unit Description 46 ...
Страница 97: ...Microprocessor Controller 96 ...
Страница 101: ...Electrical Maintenance 100 ...
Страница 141: ...Structural Accessory Maintenance 140 ...
Страница 147: ...Refrigeration System Diagnosis 146 ...
Страница 149: ...Electrical Refrigeration and Controller Menu Flow Diagrams 148 This page intentionally left blank ...
Страница 150: ...149 CRR DF MPC2000 Controller Diagram ...
Страница 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Страница 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Страница 153: ...152 CRR DF MP3000A Controller Diagram ...
Страница 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Страница 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Страница 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Страница 159: ...158 CRR DF Off Cycle Standby Flow and Pressure Diagram Page 2 of 2 CRR DF Off Cycle Standby Flow and Pressure Diagram ...
Страница 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Страница 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...