Mechanical Diagnosis
142
Compressor contactor
burned out
Low line voltage
Increase line voltage to at least 90% of
compressor motor rating
Excessive line voltage
Reduce line voltage to at least 110% of
compressor motor rating
Short cycling
Eliminate cause of short cycling
Unit short cycles
Controller out of calibration
Check controller software program
version; load new software in controller
and recheck unit performance, replace
controller
Refrigerant overcharge causing cycling on
high pressure cutout
Purge system (R-134a or R-23) with
cycling compressor
Inefficient condenser operation causing
cycling on high pressure cutout
Check condenser airflow, condenser
fan motor, condenser fan grille.
If R-23 compressor is cycling off, check
R-134a system operation and
refrigerant charge
Noisy unit
Insufficient compressor oil
Check compressor oil level on R-134a
and R-23 system. Add oil to proper
level
Loose mounting bolts
Tighten mounting bolts
Oil slugging or refrigerant flooding back
Add oil or refrigerant charge. Check
expansion valve adjustment.
Worn fan motor bearings
Replace bearings or motor
Faulty compressor
Repair or replace compressor
Condenser fan motor does
not operate
Unit in Null, Heat or Defrost
Check indicator lights. If unit is in Null,
Heat or Defrost, unit operation is
normal (no remedy required)
Loose line connection
Tighten connections
Open motor internal thermal overload
protector
Check for seized bearings or defective
thermal overload protector. Repair or
replace as necessary
Defective motor
Replace motor
Detective condenser fan contactor
Replace defective contactor
No condenser fan output signal from
controller
Diagnose and replace condenser fan
relay, main relay board or controller
Evaporator fan motor(s)
does not operate
Unit on defrost
Check operating mode indicator LEDs
Loose line connection
Tighten connections
Open motor internal thermal overload
protector
Check for seized bearings or defective
thermal overload protector. Repair or
replace as necessary
Defective motor
Replace motor
Defective low speed evaporator fan
contactor
Replace defective contactor
No low speed evaporator fan output signal
from controller
Diagnose and replace evaporator fan
relay, main relay board or controller
Condition
Possible Cause
Remedy
Содержание Thermo King CRR DF MPC2000
Страница 5: ...4 ...
Страница 11: ...List of Figures 10 ...
Страница 13: ...Introduction 12 ...
Страница 19: ...Safety Precautions 18 ...
Страница 21: ...Service Guide 20 ...
Страница 47: ...Unit Description 46 ...
Страница 97: ...Microprocessor Controller 96 ...
Страница 101: ...Electrical Maintenance 100 ...
Страница 141: ...Structural Accessory Maintenance 140 ...
Страница 147: ...Refrigeration System Diagnosis 146 ...
Страница 149: ...Electrical Refrigeration and Controller Menu Flow Diagrams 148 This page intentionally left blank ...
Страница 150: ...149 CRR DF MPC2000 Controller Diagram ...
Страница 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Страница 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Страница 153: ...152 CRR DF MP3000A Controller Diagram ...
Страница 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Страница 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Страница 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Страница 159: ...158 CRR DF Off Cycle Standby Flow and Pressure Diagram Page 2 of 2 CRR DF Off Cycle Standby Flow and Pressure Diagram ...
Страница 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Страница 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...