Refrigeration Maintenance and Service Operations
134
4. Do one of the following:
•
Pressurize the R-134a system on the low side and check for leaks
•
Pressurize the R-23 system on the high side and check for leaks.
5. If no leaks are found, recover the leak test gas from both systems (see “Refrigerant Recovery” in this
chapter).
6. Evacuate both systems (see “Evacuation and Cleanup of the Refrigeration System” in this chapter).
7. Recharge both refrigerant systems (see “Refrigerant Charge” in this chapter).
Receiver Tank Replacement (R-134a or R-23 System)
Removal
1. Recover the refrigerant charge from the unit (see “Refrigerant Recovery” in this chapter).
2. Unsolder the outlet valve on the liquid outlet line.
3. Unsolder the liquid line inlet connection.
4. Loosen the mounting nuts and remove the tank.
5. Remove the outlet valve from the receiver tank.
Installation
1. Install a new tank in the unit and tighten the mounting bolts.
2. Solder the inlet line and outlet valve line with high temperature silver solder (30% silver).
NOTE: It is strongly recommended that dry nitrogen be used to purge the system during any solder
operations (see “Using Pressurized Nitrogen” in this chapter).
NOTE: If pressurizing with nitrogen, front seat the discharge valve to prevent nitrogen from entering
the refrigerant charge.
3. Pressurize the refrigeration system and check for leaks (see “Refrigerant Leak Test Procedure” in this
chapter).
4. Evacuate the system (see “Evacuation and Cleanup of the Refrigeration System” in this chapter).
5. Recharge the unit (see “Refrigerant Charge” in this chapter).
High Pressure Cutout Switch Replacement
(R-134a or R-23 System)
Removal
1. Close the suction service valve and pump down the compressor:
CAUTION: Any time the discharge valve is front seated, disconnect the unit power source to
prevent accidental compressor start-up.
CAUTION: Any time the discharge valve is front seated, disconnect the unit power source to
prevent accidental compressor start-up.
Содержание Thermo King CRR DF MPC2000
Страница 5: ...4 ...
Страница 11: ...List of Figures 10 ...
Страница 13: ...Introduction 12 ...
Страница 19: ...Safety Precautions 18 ...
Страница 21: ...Service Guide 20 ...
Страница 47: ...Unit Description 46 ...
Страница 97: ...Microprocessor Controller 96 ...
Страница 101: ...Electrical Maintenance 100 ...
Страница 141: ...Structural Accessory Maintenance 140 ...
Страница 147: ...Refrigeration System Diagnosis 146 ...
Страница 149: ...Electrical Refrigeration and Controller Menu Flow Diagrams 148 This page intentionally left blank ...
Страница 150: ...149 CRR DF MPC2000 Controller Diagram ...
Страница 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Страница 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Страница 153: ...152 CRR DF MP3000A Controller Diagram ...
Страница 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Страница 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Страница 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Страница 159: ...158 CRR DF Off Cycle Standby Flow and Pressure Diagram Page 2 of 2 CRR DF Off Cycle Standby Flow and Pressure Diagram ...
Страница 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Страница 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...