Refrigeration Maintenance and Service Operations
131
Installation
1. Remove the sealing caps from the new dehydrator.
2. Do one of the following:
•
R-134a System: Apply clean compressor oil to dehydrator threads. Assemble new dehydrator to
lines. Finger tighten mounting nuts.
•
R-23 System: Clean tubes for soldering. Position filter drier in liquid line. Solder filter drier in
liquid line.
NOTE: To prevent incorrect installation of the dehydrator, the inlet and outlet fittings are different
sizes.
3. Reinstall dehydrator clamping brackets, nut and bolts. Tighten the bolts.
4. Do one of the following:
•
R-134a System:
a. Tighten the dehydrator inlet line mounting nut. Open the liquid line service valve on the inlet side
of the dehydrator slowly to release a small amount of refrigerant from the receiver tank to purge
the air through the filter. Then tighten the outlet nut.
NOTE: R-134a — When removing or replacing the o-ring nuts on the dehydrator, always hold the
body of the dehydrator near the flange fittings to prevent twisting the tubing when the nuts are
being loosened or tightened.
b. Back seat (open) the liquid line service valve on the inlet side of the dehydrator.
c. Test the dehydrator for leaks (see “Refrigerant Leak Test Procedure” in this chapter).
d. If no leaks are found, place the unit in operation.
•
R-23 System:
a. Pressurize the system and test for leaks (see “Refrigerant Leak Test Procedure” in this chapter).
b. If no leaks are found, recover the leak test gas (see “Refrigerant Recovery” in this chapter).
c. Then evacuate the system (see “Evacuation and Cleanup of the Refrigeration System” in this
chapter).
d. Recharge the unit with R-23 refrigerant and check the compressor oil level. Add oil if necessary.
Expansion Valve Replacement (R-134a or R-23 Systems)
Removal
1. Do one of the following:
•
R-134a System: Close the liquid line service valve and pump down the low side. Open the outlet
valve slightly to equalize the pressure between 10 and 20 kPa, 0.10 and 0.20 bar, 1 and 3 psig.
•
R-23 System: Recover the refrigerant charge from the unit (do NOT vent refrigerant to the
atmosphere).
2. Remove insulating tape and encamp feeler bulb from the suction line. Note the position of the feeler
bulb on the side of the suction line.
3. Remove insulating tape from expansion valve outlet line.
Содержание Thermo King CRR DF MPC2000
Страница 5: ...4 ...
Страница 11: ...List of Figures 10 ...
Страница 13: ...Introduction 12 ...
Страница 19: ...Safety Precautions 18 ...
Страница 21: ...Service Guide 20 ...
Страница 47: ...Unit Description 46 ...
Страница 97: ...Microprocessor Controller 96 ...
Страница 101: ...Electrical Maintenance 100 ...
Страница 141: ...Structural Accessory Maintenance 140 ...
Страница 147: ...Refrigeration System Diagnosis 146 ...
Страница 149: ...Electrical Refrigeration and Controller Menu Flow Diagrams 148 This page intentionally left blank ...
Страница 150: ...149 CRR DF MPC2000 Controller Diagram ...
Страница 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Страница 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Страница 153: ...152 CRR DF MP3000A Controller Diagram ...
Страница 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Страница 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Страница 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Страница 159: ...158 CRR DF Off Cycle Standby Flow and Pressure Diagram Page 2 of 2 CRR DF Off Cycle Standby Flow and Pressure Diagram ...
Страница 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Страница 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...