Refrigeration Maintenance and Service Operations
126
3. Set the R-23 refrigerant tank for gas charging. Open the refrigerant tank hand valve.
4. Observe the bottom receiver tank sight glass. When refrigerant is visible in the bottom of the lower
sight glass, close the hand valve on the refrigerant tank.
5. Remove the refrigerant hose from the receiver tank
6. Cap the receiver tank service port.
7. Check and correct the refrigerant charge level after the cargo has been unloaded and the unit is OFF.
Using Pressurized Nitrogen
The improper use of high pressure cylinders can cause physical damage to components, or personal
injury, or cause stress that would lead to failure of components.
Safety Precautions
Observe the proper handling of cylinders:
1. Always keep protective cap on cylinder when not in use.
2. Secure cylinder in proper storage area or fastened to cart.
3. DO NOT expose to excessive heat or direct sun light.
4. DO NOT drop, dent, or damage cylinder.
5. Use a pressure regulator and a safety pressure relief valve as part of the pressure testing equipment.
The safety pressure relief valve should be of the non-adjustable, non-tempering type. The valve
should bypass any time the pressure exceeds its setting.
6. Open valve slowly; use regulators and safety valves that are in good working order.
7. The regulator should have two gauges; one to read tank pressure, the other to read line pressure.
Properly maintained equipment will allow leak testing, purging, or dehydration to be done safely.
CAUTION: Immediately stop adding refrigerant when refrigerant is visible in the bottom of the
lower sight glass. Under normal operating conditions, R-23 refrigerant will rarely be visible in
the lower sight glass on a fully charged system.
CAUTION: Nitrogen (N2) is under 15,170 kPa, 151.70 bar, 2200 psig, or greater. Pressure is
for full cylinder at 21 C (70 F). DO NOT use Oxygen (O2), acetylene or any other types of
pressurized gas on refrigeration systems or any component of a system.
Содержание Thermo King CRR DF MPC2000
Страница 5: ...4 ...
Страница 11: ...List of Figures 10 ...
Страница 13: ...Introduction 12 ...
Страница 19: ...Safety Precautions 18 ...
Страница 21: ...Service Guide 20 ...
Страница 47: ...Unit Description 46 ...
Страница 97: ...Microprocessor Controller 96 ...
Страница 101: ...Electrical Maintenance 100 ...
Страница 141: ...Structural Accessory Maintenance 140 ...
Страница 147: ...Refrigeration System Diagnosis 146 ...
Страница 149: ...Electrical Refrigeration and Controller Menu Flow Diagrams 148 This page intentionally left blank ...
Страница 150: ...149 CRR DF MPC2000 Controller Diagram ...
Страница 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Страница 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Страница 153: ...152 CRR DF MP3000A Controller Diagram ...
Страница 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Страница 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Страница 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Страница 159: ...158 CRR DF Off Cycle Standby Flow and Pressure Diagram Page 2 of 2 CRR DF Off Cycle Standby Flow and Pressure Diagram ...
Страница 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Страница 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...