Microprocessor Controller
89
07*
R-134 Compressor Current Too Low
(Check Alarm)
• Occurs during Pretrip (PTI) only.
• Compressor power consumption is higher than
approximately 7 amps.
• Indicates:
• Defective or open fuse CB 6A, high pressure
cutout switch or connection in plug J19
between pins 7 & 8
• No signal on plug J11 on pin 8
• Defective compressor relay
• Defective volt or amp meter on relay board
• Low R-134a refrigerant charge
• Defective R-134a compressor or valve plate
• Start “Manual Function Test”.
Make sure the compressor relay energizes. If
relay does NOT energize and the LED above
the compressor relay is NOT ON, check for a
defective cable No. 2, main relay board or
controller.
• Check discharge and suction pressure gauge
readings on R-134a system. Evaluate readings
based on current cargo and ambient
temperatures.
• Check compressor volts and amps.
• Check power supply volts.
*If both alarms 06 and 07 are activated, the alarms are caused by a large difference in measured amps. Start “Manual
Function Test” and start the R-134a compressor and condenser fan. Check the compressor amps measurement. If necessary,
check the resistance of the compressor motor windings.
10*
Heater Current Too High
(Check Alarm)
• Occurs during Pretrip (PTI) only.
• Heater power consumption is higher than
approximately 9 amps and lower than 13 amps.
• Indicates:
• Incorrect heaters or heater connections
• Defective volt or amp meter on relay board
• Defective heater element
• Start “Manual Function Test” and turn heaters
ON. Check current draw on each phase.
Current draw should be about 9.0 amps on
each phase at 380V (10.4 amps at 460V).
11*
Heater Current Too Low
(Check Alarm)
• Occurs during Pretrip (PTI) only.
• Heater power consumption is lower than
approximately 6 to 9 amps, depending on
voltage.
• Indicates:
• Incorrect heaters or heater connections
• Defective heater elements or heat relay
• Defective wire connections
• Defective high evaporator temperature switch
• Start “Manual Function Test” and turn heaters
ON. Check current draw on each phase.
Current draw should be 4.5 amps on each
phase at 380V.
• If heat relay fails to energize, check evaporator
high temperature switch. Switch should be
closed at temperatures below 54 C (130 F);
there should be continuity between pins 5 & 6 in
plug J19.
• Check power supply volts and amps.
• Check heater element resistance between H1
and H2, H2 and H3, and H1 and H3.
Resistance readings should be equal
(approximately 50 ohms).
*If both alarms 10 and 11 are activated, the alarms are caused by a large difference in measured amps. Start “Manual
Function Test” and energize the heaters. Check the heater amps measurement. If necessary, isolate and check the resistance
of each individual heater element.
Code
Description
Corrective Action
Содержание Thermo King CRR DF MPC2000
Страница 5: ...4 ...
Страница 11: ...List of Figures 10 ...
Страница 13: ...Introduction 12 ...
Страница 19: ...Safety Precautions 18 ...
Страница 21: ...Service Guide 20 ...
Страница 47: ...Unit Description 46 ...
Страница 97: ...Microprocessor Controller 96 ...
Страница 101: ...Electrical Maintenance 100 ...
Страница 141: ...Structural Accessory Maintenance 140 ...
Страница 147: ...Refrigeration System Diagnosis 146 ...
Страница 149: ...Electrical Refrigeration and Controller Menu Flow Diagrams 148 This page intentionally left blank ...
Страница 150: ...149 CRR DF MPC2000 Controller Diagram ...
Страница 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Страница 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Страница 153: ...152 CRR DF MP3000A Controller Diagram ...
Страница 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Страница 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Страница 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Страница 159: ...158 CRR DF Off Cycle Standby Flow and Pressure Diagram Page 2 of 2 CRR DF Off Cycle Standby Flow and Pressure Diagram ...
Страница 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Страница 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...