Microprocessor Controller
90
14*
Evaporator Fan Low Speed Current Too High
(Check Alarm)
• Occurs during Pretrip (PTI) only.
• Evaporator fan power consumption is higher
than approximately 2.6 to 2.9 amps, depending
on voltage.
• Indicates:
• Defective or stuck evaporator fan motor
• Incorrect motor or motor connections
• Motor high and low speed connection are
interchanged
• Defective volt or amp meter on relay board
• Open evaporator door and make sure all fans
rotate freely.
• Start “Manual Function Test” and set evaporator
motors to low speed. Make sure all fans start on
low speed.
• Check fan motor volts and amps.
• Check power supply volts and amps.
15*
Evaporator Fan Low Speed Current Too Low
(Check Alarm)
• Occurs during Pretrip (PTI) only.
• Evaporator fan power consumption is lower than
approximately 1.0 to 1.2 amps, depending on
voltage.
• Indicates:
• Defective evaporator fan motor relay
• Defective or open fan motor internal over
temperature protection switch
• Defective volt or amp meter on relay board
• Incorrect motor or motor connections
• Open evaporator door and make sure all fans
rotate freely.
• Start “Manual Function Test” and set evaporator
motors to low speed. Make sure all fans start on
low speed.
• Check fan motor volts and amps.
• Check power supply volts and amps.
*If both alarms 14 and 15 are activated, the alarms are caused by a large difference in measured amps. Start “Manual
Function Test” and start the evaporator fans. Check the evaporator fan amps measurement. If necessary, check the
resistance in the motors between L1, L2 and L3, and L1 and L3. Resistance readings should be equal (approximately 30
Ohms, total of 3 motors).
Code
Description
Corrective Action
Содержание Thermo King CRR DF MPC2000
Страница 5: ...4 ...
Страница 11: ...List of Figures 10 ...
Страница 13: ...Introduction 12 ...
Страница 19: ...Safety Precautions 18 ...
Страница 21: ...Service Guide 20 ...
Страница 47: ...Unit Description 46 ...
Страница 97: ...Microprocessor Controller 96 ...
Страница 101: ...Electrical Maintenance 100 ...
Страница 141: ...Structural Accessory Maintenance 140 ...
Страница 147: ...Refrigeration System Diagnosis 146 ...
Страница 149: ...Electrical Refrigeration and Controller Menu Flow Diagrams 148 This page intentionally left blank ...
Страница 150: ...149 CRR DF MPC2000 Controller Diagram ...
Страница 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Страница 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Страница 153: ...152 CRR DF MP3000A Controller Diagram ...
Страница 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Страница 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Страница 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Страница 159: ...158 CRR DF Off Cycle Standby Flow and Pressure Diagram Page 2 of 2 CRR DF Off Cycle Standby Flow and Pressure Diagram ...
Страница 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Страница 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...