Refrigeration Maintenance and Service Operations
133
3. Heat and unsolder liquid inlet and outlet line connections.
4. Heat and unsolder the suction line connections.
5. Lift the heat exchanger assembly from the unit.
Installation
1. Clean the tubes for soldering.
2. Place the heat exchanger assembly in the unit and install the mounting hardware.
3. Solder the suction line connections.
NOTE: It is strongly recommended that dry nitrogen be used to purge the system during any solder
operations (see “Using Pressurized Nitrogen” in this chapter).
NOTE: If pressurizing with nitrogen, front seat the discharge valve to prevent nitrogen from entering
the refrigerant charge.
4. Solder the liquid line connections.
5. Pressurize the low side and check for leaks (see “Refrigerant Leak Test Procedure” in this chapter).
6. If no leaks are found, recover the leak test gas (see “Refrigerant Recovery” in this chapter).
7. Evacuate the low side (see “Evacuation and Cleanup of the Refrigeration System” in this chapter).
8. Recharge the unit (see “Refrigerant Charge” in this chapter).
R-23 System to R-134a System Plate Heat Exchanger Replacement
Removal
1. Recover the refrigerant charge from the both refrigeration systems (see “Refrigerant Recovery” in this
chapter).
2. Remove the panel that protects the heat exchanger assembly in the power cord storage compartment.
3. Heat and unsolder all system inlet and outlet line connections.
4. Remove the heat exchanger assembly from the unit.
Installation
1. Clean the tubes for soldering.
2. Place the heat exchanger assembly in the unit and position in refrigeration system tubing.
3. Solder all refrigerant line connections.
NOTE: It is strongly recommended that dry nitrogen be used to purge the system during any solder
operations (see “Using Pressurized Nitrogen” in this chapter).
NOTE: If pressurizing with nitrogen, front seat the discharge valve to prevent nitrogen from entering
the refrigerant charge.
CAUTION: Any time the discharge valve is front seated, disconnect the unit power source to
prevent accidental compressor start-up.
Содержание Thermo King CRR DF MPC2000
Страница 5: ...4 ...
Страница 11: ...List of Figures 10 ...
Страница 13: ...Introduction 12 ...
Страница 19: ...Safety Precautions 18 ...
Страница 21: ...Service Guide 20 ...
Страница 47: ...Unit Description 46 ...
Страница 97: ...Microprocessor Controller 96 ...
Страница 101: ...Electrical Maintenance 100 ...
Страница 141: ...Structural Accessory Maintenance 140 ...
Страница 147: ...Refrigeration System Diagnosis 146 ...
Страница 149: ...Electrical Refrigeration and Controller Menu Flow Diagrams 148 This page intentionally left blank ...
Страница 150: ...149 CRR DF MPC2000 Controller Diagram ...
Страница 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Страница 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Страница 153: ...152 CRR DF MP3000A Controller Diagram ...
Страница 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Страница 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Страница 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Страница 159: ...158 CRR DF Off Cycle Standby Flow and Pressure Diagram Page 2 of 2 CRR DF Off Cycle Standby Flow and Pressure Diagram ...
Страница 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Страница 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...