Microprocessor Controller
60
All data logs include the time and date; setpoint temperature; and supply, return, USDA1, USDA2 and
USDA3 sensor temperatures. All temperature logs can be viewed from the controller’s LCD message
display.
If the unit power supply is disconnected, the datalogger will continue to register 168 temperature logs.
These will be maintained until the unit is re-connected to power, and the battery automatically
re-charged.
Trip data can be retrieved (but not erased) from the datalogger memory using DRU-II or SmartSponge
handheld data retriever; or via the REFCON remote monitor system. The datalogger is also equipped
with a high-speed parallel communication port. Data transfer time is approx. 25 seconds for event
logs and approx. 70 seconds for temperature logs.
Trip data from separate units is denoted by the identification information entered into the controller at
the beginning of the trip via the general purpose keypad. Identification data may include the container
ID number, location B.R.T., contents, loading data, voyage no., ship, load port, discharge port and
comments. The container ID number is stored in the Configuration submenu.
12. Electronic phase selection: The microprocessor controller monitors the phase of the power supply to
ensure proper rotation of the condenser and evaporator fans, and the compressor.
13. Sequential component start-up control: A sequence start of the required loads occurs during initial
start-up of the controller and when a control mode shift requires the compressors to start (see
“Sequence of Operation” in this chapter).
14. Hourmeters: The microprocessor controller has multiple built-in hourmeters that can be accessed
through the Main Menu.
15. Manual emergency control capability. Manual control settings in the control box allow the unit to
operate even in the event of a fatal failure of the controller. Manual control offers three operating
functions: Heat, Defrost and Cool (see “Manual Emergency Mode Operation” in this chapter).
16. Flash memory: Flash program memory allows the application software to be updated without
replacing a EPROM chip on the controller. Application software can be updated in the field using a
portable computer and the MPC2000 or MPC2000ID Loader program. Consequently, the field
installed application software version may have a different revision number and may include control
features not included in the original factory installed software. If the operation of your unit differs
from the Sequence of Operation described for the unit in this manual, enter “Misc. Functions” in the
Main Menu to check that the program version is correct (see “Menu Operating Instructions” in this
chapter).
17. Display menus: The microprocessor controller contains an extensive display menu that can be
navigated via keypad. The display menu is organized into 7 Main Menus:
•
Data Menu: Menu screens in this group are used to display unit operating information including
sensor temperatures, voltage, current and frequency information.
•
Alarm List Menu: Menu screens in this group display a list of alarm code(s).
•
Commands Menu: Menu screens in this group are used to activate defrost, function tests, pretrip
(PTI) tests and manual function test.
•
Miscellaneous Functions Menu: Menu screens in this group display date/time, C/F, cargo data,
program version and run time (hourmeters) information.
•
Configuration Menu: Menu screens in this group display refrigerant type, in-range setting,
container ID, contrast (screen), language, unit type, reefer type and zero current status.
Содержание Thermo King CRR DF MPC2000
Страница 5: ...4 ...
Страница 11: ...List of Figures 10 ...
Страница 13: ...Introduction 12 ...
Страница 19: ...Safety Precautions 18 ...
Страница 21: ...Service Guide 20 ...
Страница 47: ...Unit Description 46 ...
Страница 97: ...Microprocessor Controller 96 ...
Страница 101: ...Electrical Maintenance 100 ...
Страница 141: ...Structural Accessory Maintenance 140 ...
Страница 147: ...Refrigeration System Diagnosis 146 ...
Страница 149: ...Electrical Refrigeration and Controller Menu Flow Diagrams 148 This page intentionally left blank ...
Страница 150: ...149 CRR DF MPC2000 Controller Diagram ...
Страница 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Страница 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Страница 153: ...152 CRR DF MP3000A Controller Diagram ...
Страница 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Страница 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Страница 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Страница 159: ...158 CRR DF Off Cycle Standby Flow and Pressure Diagram Page 2 of 2 CRR DF Off Cycle Standby Flow and Pressure Diagram ...
Страница 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Страница 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...