Microprocessor Controller
94
56
Compressor Temperature Too High
(Shutdown Alarm)
• R-134a compressor discharge line temperature
is above 130 C (266 F). R-134a compressor
operation should resume when discharge line
temperature decreases below 90 C (194 F); or
R-23 compressor discharge line temperature is
above 138 C (280 F). R-23 compressor
operation should resume when discharge line
temperature decreases below 138 C (280 F).
• Indicates:
• Air in refrigeration system
• Low refrigerant charge in R-134a system
• R-134a Only: Defective compressor or valve
plate
• Wrong or defective sensor
• Operate unit on Cool and check discharge and
suction pressure gauge readings on R-134a
refrigeration system. Check refrigerant charge
of R-134a system and R-23 system.
• Check sensor resistance. Resistance must be
100,000 ohms at 25 C (77 F).
• Check discharge line temperature with a
separate electronic thermometer and compare
to “HIGH PR TEMP” showing in the View
submenu of controller for both the R-134a
compressor and the R-23 compressor.
58
Phase Sensor Error
(Check Alarm)
• Occurs during Pre-trip (PTI) test only.
• During Phase Sensor Test, amperage difference
between correct and wrong condenser fan
rotation is more than 0.2 amps.
• Indicates:
• Defective relay board
• Defective relay board cable No. 2
• Defective phase relay
• Start “Manual Function Test” and view current
display for each phase to determine if each
phase sensor relay is receiving a signal.
Change incoming power phase. Verify that the
phase relays respond correctly.
59
Delta Current Error
(Log Alarm)
• Power consumption is More than 50% above or
below (Min 0,8 Amp).
• Indicates:
• Open connection on one phase of power
supply to a 3-phase unit component including
R-134a compressor or R-23 compressor.
• Start manual function test one by one to verify
correct current draw for all components and
current draw reading of 0 Amp when
component is disengaged.
97
Compressor Sensor Open Circuit
(Log Alarm)
• Sensor circuit resistance is higher than
10,000,000 ohms on R-134a or R-23
compressor.
• Temperature below -30 C (-22 F).
• Indicates:
• Open circuit to sensor
• Defective or wrong sensor
• Defective relay board
• Defective cable No. 1
• Defective controller
• Check sensor resistance between pins 9 and
10 on plug J15 for R-134a compressor sensor
and between pins 11 and 12 on plug J15 for
R-23 compressor. Resistance must be 100,000
ohms at 25 C (77 F).
• Check cable No. 1 between controller and relay
board.
NOTE: Unit will operate normally without
compressor sensor. However, controller
compressor high temperature protection is
not active.
Code
Description
Corrective Action
Содержание Thermo King CRR DF MPC2000
Страница 5: ...4 ...
Страница 11: ...List of Figures 10 ...
Страница 13: ...Introduction 12 ...
Страница 19: ...Safety Precautions 18 ...
Страница 21: ...Service Guide 20 ...
Страница 47: ...Unit Description 46 ...
Страница 97: ...Microprocessor Controller 96 ...
Страница 101: ...Electrical Maintenance 100 ...
Страница 141: ...Structural Accessory Maintenance 140 ...
Страница 147: ...Refrigeration System Diagnosis 146 ...
Страница 149: ...Electrical Refrigeration and Controller Menu Flow Diagrams 148 This page intentionally left blank ...
Страница 150: ...149 CRR DF MPC2000 Controller Diagram ...
Страница 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Страница 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Страница 153: ...152 CRR DF MP3000A Controller Diagram ...
Страница 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Страница 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Страница 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Страница 159: ...158 CRR DF Off Cycle Standby Flow and Pressure Diagram Page 2 of 2 CRR DF Off Cycle Standby Flow and Pressure Diagram ...
Страница 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Страница 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...