Mechanical Diagnosis
Condition
Possible Cause
Remedy
One or Both Compressors
do not operate — no
amperage draw
Controller on; unit start sequence still
timing
Wait at least 1 minute for both
compressors to start
No power to unit (condenser and
evaporator fans do not operate)
Locate fault and repair: power source,
power plug, main circuit breaker, motor
contactor, motor terminals, motor
Open in 24 Vac control circuit
Check fuses and On/Off switch.
Replace or repair as required
Container temperature does not demand
compressor operation
Adjust controller setpoint
Compressor contactor inoperative
Replace compressor contactor
No output signal from controller
Diagnose and replace main relay board
or controller
Unit on defrost
Turn Unit On/Off switch Off and then
On again
Detective high pressure cutout switch in
R-134a or R-23 system
Replace defective switch
High condenser head pressure causing
high pressure cutout on R-134a or R-23
system
Check refrigeration system and correct
fault
Defective R-134a or R-23 compressor
Replace compressor
Controller shut unit down on Compressor
Over Temperature (fault code 56)
Let compressor cool and controller will
reset automatically. Check compressor
temperature sensor, R-134a refrigerant
charge, R-23 refrigerant charge
Compressor motor internal thermal
overload protection open
If compressor contactor is energized,
wait 60 minutes for protector to cool
and reset.
Low suction pressure or defective low
pressure cutout on R-23 system (CRR DF
MPC2000ID Units Only)
Check R-23 refrigeration system for
leaks or and obstruction in the low or
high side. Replace a defective low
pressure cutout switch
Compressor does not
operate; excessive
amperage draw or
intermittent cycling on
overload
Piston stuck (R-134 System)
Rotating Scroll Stuck (R-23 System)
R-134a System: Remove compressor
head and look for broken valve and
jammed parts R-23 System: Replace
compressor
Seized or frozen compressor bearings
Replace compressor
Improperly wired
Check/correct wiring against wiring
diagram
Low line voltage
Check line voltage — determine
location of voltage drop
High head pressure
Eliminate cause of high head pressure
Contacts in compressor contactor not
closing completely
Check by operating manually. Repair or
replace.
Open circuit in compressor motor winding Check motor stator connections. Check
stator winding for continuity. If open,
replace compressor
Defective compressor motor internal
thermal overload protector
Replace thermal overload protector or
compressor
R 23 compressor not running Auxiliary contact on R134a open
Check curcuit, replace contact.
Содержание Thermo King CRR DF MPC2000
Страница 5: ...4 ...
Страница 11: ...List of Figures 10 ...
Страница 13: ...Introduction 12 ...
Страница 19: ...Safety Precautions 18 ...
Страница 21: ...Service Guide 20 ...
Страница 47: ...Unit Description 46 ...
Страница 97: ...Microprocessor Controller 96 ...
Страница 101: ...Electrical Maintenance 100 ...
Страница 141: ...Structural Accessory Maintenance 140 ...
Страница 147: ...Refrigeration System Diagnosis 146 ...
Страница 149: ...Electrical Refrigeration and Controller Menu Flow Diagrams 148 This page intentionally left blank ...
Страница 150: ...149 CRR DF MPC2000 Controller Diagram ...
Страница 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Страница 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Страница 153: ...152 CRR DF MP3000A Controller Diagram ...
Страница 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Страница 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Страница 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Страница 159: ...158 CRR DF Off Cycle Standby Flow and Pressure Diagram Page 2 of 2 CRR DF Off Cycle Standby Flow and Pressure Diagram ...
Страница 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Страница 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...