Refrigeration Maintenance and Service Operations
125
10. Close the refrigerant tank hand valve.
11. Back seat the suction service valve. Then stop the compressor.
12. Remove the hoses from the receiver outlet and discharge service valves. Cap the receiver outlet
service port.
13. Wait for the plate-type R-134a / R-23 system heat exchanger to warm above 0 C (32 F). This can take
up to 30 minutes.
See R-23 final charging procedure for partially charged units for empty or loaded containers to complete
charging procedure.
R-23 Final Charging Procedure for Partially Charged Units on Empty
Containers
NOTE: The R-23 refrigerant should be charged with the container empty, the unit OFF and all
refrigeration system components above -5 C (23 F). The R-134a compressor must not have been
operated within the past 30 minutes and there must not be frost on the plate-type R-134a / R-23 heat
exchanger tubing.
1. Before attempting to add R23 refrigerant with loaded container check for good cooling capacity by
verifying if Suction discharge pressure is in line with specification.
2. Connect a refrigerant hose to a R-23 refrigerant tank.
3. Connect the refrigerant hose to the suction line service port. Be sure to purge the air from the
refrigerant hose.
4. Mid-seat the suction service valve.
5. Set the R-23 refrigerant tank for gas charging. Open the refrigerant tank hand valve.
6. Observe both the suction and discharge pressures on the unit gauges. When the unit pressure reaches
1700 kPa, 17 bar, 247 psig, close the hand valve on the refrigerant tank. With the unit OFF, the suction
and discharge readings should be equal.
The R-23 refrigerant pressure in the unit during charging with the unit OFF will vary with the ambient
temperature:
7. Remove the gauge manifold set.
8. Cap all service ports and valve stems.
R-23 Charging Procedure for Partially Charged Units on Loaded Containers
NOTE: R-23 refrigerant should be added to an operating unit on a loaded container only if the unit is
unable to maintain a -55 C to -60 C (-62 F to -76 F) load temperature. The risk of overcharging the
system with R-23 is too large.
1. Connect a refrigerant hose to a R-23 refrigerant tank.
2. Connect the refrigerant hose to the receiver tank service fitting. Be sure to purge the air from the hose.
Ambient Temperature R-23 System Pressure
O C (32 F)
1600 kPa, 16 bar, 232 psig
20 C (68 F)
1700 kPa, 17 bar, 247 psig
38 C (100 F)
1800 kPa, 18 bar, 261 psig
Содержание Thermo King CRR DF MPC2000
Страница 5: ...4 ...
Страница 11: ...List of Figures 10 ...
Страница 13: ...Introduction 12 ...
Страница 19: ...Safety Precautions 18 ...
Страница 21: ...Service Guide 20 ...
Страница 47: ...Unit Description 46 ...
Страница 97: ...Microprocessor Controller 96 ...
Страница 101: ...Electrical Maintenance 100 ...
Страница 141: ...Structural Accessory Maintenance 140 ...
Страница 147: ...Refrigeration System Diagnosis 146 ...
Страница 149: ...Electrical Refrigeration and Controller Menu Flow Diagrams 148 This page intentionally left blank ...
Страница 150: ...149 CRR DF MPC2000 Controller Diagram ...
Страница 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Страница 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Страница 153: ...152 CRR DF MP3000A Controller Diagram ...
Страница 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Страница 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Страница 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Страница 159: ...158 CRR DF Off Cycle Standby Flow and Pressure Diagram Page 2 of 2 CRR DF Off Cycle Standby Flow and Pressure Diagram ...
Страница 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Страница 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...