Refrigeration Maintenance and Service Operations
108
NOTE: These gauges may be removed and reinstalled without additional purging so long as a slight
positive pressure remains in the manifold and hoses when removed from the unit.
Gauge Manifold Set Removal
NOTE: To ensure minimum refrigerant release to the atmosphere, THE SYSTEM SHOULD BE
RUNNING. However, this is not possible in all cases, but the same procedure should be followed.
1. Rotate discharge hose fitting hand wheel counterclockwise to withdraw the fitting stem from the
discharge line port valve. Then open both service manifold valves to center port.
2. Close the receiver tank outlet valve and pump down the low side. Then turn the unit OFF.
3. Rotate the discharge fitting hand wheel counterclockwise to depress the port valve stem to equalize
pressure at 21 kPa, 0.21 bar, 3 psig.
4. Rotate both coupler hand wheels counterclockwise to close (seal) the valve port stems to the high and
low hoses.
5. Remove the gauge lines from the suction and discharge service fittings and cap the service ports.
6. Back seat receiver tank outlet valve and cap valve stem.
7. Secure all manifold lines to manifold hose anchors when the manifold is not in use.
Service Procedure Guide
Typical R-23 and R-134a System Suction and Discharge Pressure
Readings
Test Procedure
1. Operate unit in COOL for 10 minutes or more.
2. Maintain discharge pressure (shown in table below) for a 80-100 F (27-38 C) ambient temperature by
covering the condenser coil.
3. Compare unit suction pressure with approximate expected reading (shown in table below).
4. A cool, moist line is normal. A frosted or abnormally dry line and out-of-range pressures indicate a
problem in the refrigeration system.
NOTE: Control condenser air flow to maintain condenser temperature (R-134a System) near a
27-38oC (80-100oF) ambient while reading discharge and suction pressures.
Scroll Compressor (R-23 Refrigeration System)
Procedure
Repair/Service Action
Reclaim Refrigerant
Open the high side of the refrigeration system.
Reclaim Refrigerant
Open the low side of the refrigeration system.
Reciprocating Compressor (R-134a Refrigeration System)
Procedure
Repair/Service Action
Reclaim Refrigerant
Open the high side of the refrigeration system.
Low Side Pump Down
Open the low side of the refrigeration system.
Содержание Thermo King CRR DF MPC2000
Страница 5: ...4 ...
Страница 11: ...List of Figures 10 ...
Страница 13: ...Introduction 12 ...
Страница 19: ...Safety Precautions 18 ...
Страница 21: ...Service Guide 20 ...
Страница 47: ...Unit Description 46 ...
Страница 97: ...Microprocessor Controller 96 ...
Страница 101: ...Electrical Maintenance 100 ...
Страница 141: ...Structural Accessory Maintenance 140 ...
Страница 147: ...Refrigeration System Diagnosis 146 ...
Страница 149: ...Electrical Refrigeration and Controller Menu Flow Diagrams 148 This page intentionally left blank ...
Страница 150: ...149 CRR DF MPC2000 Controller Diagram ...
Страница 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Страница 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Страница 153: ...152 CRR DF MP3000A Controller Diagram ...
Страница 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Страница 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Страница 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Страница 159: ...158 CRR DF Off Cycle Standby Flow and Pressure Diagram Page 2 of 2 CRR DF Off Cycle Standby Flow and Pressure Diagram ...
Страница 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Страница 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...