47
Operating Instructions
Basic Unit Controls, Instruments and Protection Devices
Unit Control Box
ON/OFF Switch:
ON position. Unit will operate on cool or null depending on the controller setpoint
temperature and the container air temperature. OFF position. The unit will not operate.
Control System Circuit Breaker:
A 7 ampere manual reset circuit breaker protects the control circuit. This
circuit breaker is located in the control box beside the On/Off switch.
Main Circuit Breaker:
A 32 ampere manual reset circuit breaker protects the 460/380V power supply
circuit to the unit electric motors and control system transformer. The main power circuit breaker is
located in the control box.
Fuses:
A number of fuses are located on the main relay board and controller plug to protect unit circuits
and components.
•
Three 20 amp fuses protect high voltage circuits on the main relay board.
•
A 2 amp fuse protects the controller’s 28 V system.
•
A 2 amp fuse protects the controller’s battery charging circuit.
Overload Protection:
The condenser fan motor, evaporator fan motors and compressor motors include
internal overload protection with automatic reset.
Phase Sequence Selection:
When the On/Off switch is turned ON, phase sensors on the main relay board
determine the incoming power phase to ensure proper condenser fan, evaporator fan and compressor
rotation.
MPC2000, MPC2000ID or MP3000 Controller
A MPC2000, MPC2000ID or MP3000 microprocessor controls all unit functions to maintain the cargo at
the proper temperature. The controller also monitors and records system faults and performs pre-trip.
Keypad:
Sixteen general purpose keys are used to display information, change the setpoint, change
programmable features and initiate control tasks.
°C–°F Key:
Press this key to view temperatures in the LED display in the alternate temperature value.
Alternate value (C or F) shows while the key is pressed.
RET/SUP Key:
Press this key to view the alternate sensor temperature in the LED display. Alternate sensor
(return or supply) shows while the key is pressed.
Defrost Key:
Press this key to initiate a manual defrost cycle. If the evaporator coil temperature is below
10 C (50 F), the unit will defrost. Otherwise the controller will display “Defrost Not Activated” in the
LCD display and the unit will continue normal operation.
Setpoint Key:
Press this key to change the setpoint. Cursor in the LCD display automatically appears in
the “TEMP SETP” line of the Data menu. See “Changing the Setpoint” in the Microprocessor Controller
chapter for complete instructions.
Status Indicator LEDs:
located in the large LED display signal:
•
Supply (Air Temperature)
•
Return (Air Temperature)
•
Humidity Mode (Inactive on CRR DF units)
•
Compressor (Cooling On)
Содержание Thermo King CRR DF MPC2000
Страница 5: ...4 ...
Страница 11: ...List of Figures 10 ...
Страница 13: ...Introduction 12 ...
Страница 19: ...Safety Precautions 18 ...
Страница 21: ...Service Guide 20 ...
Страница 47: ...Unit Description 46 ...
Страница 97: ...Microprocessor Controller 96 ...
Страница 101: ...Electrical Maintenance 100 ...
Страница 141: ...Structural Accessory Maintenance 140 ...
Страница 147: ...Refrigeration System Diagnosis 146 ...
Страница 149: ...Electrical Refrigeration and Controller Menu Flow Diagrams 148 This page intentionally left blank ...
Страница 150: ...149 CRR DF MPC2000 Controller Diagram ...
Страница 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Страница 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Страница 153: ...152 CRR DF MP3000A Controller Diagram ...
Страница 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Страница 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Страница 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Страница 159: ...158 CRR DF Off Cycle Standby Flow and Pressure Diagram Page 2 of 2 CRR DF Off Cycle Standby Flow and Pressure Diagram ...
Страница 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Страница 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...