Specifications
22
R-23 Refrigeration System
Compressor Model No.
ZM18K4E-TFD-N275, Hermetic Scroll
Refrigerant Charge
Evacuated System
Add Partial Charge by Pressure
3.2 Kg (7.05 lb) R-23
Charge to 1700 kPa, 17.00 bar, 247 psig
Compressor Oil Capacity
1.77 liter (60 oz.)*
Compressor Oil Type
Polyol Ester Based Type (required), TK Part No.
203-433**
Typical System Pressures at 37.8 C (100 F) Ambient
Standby (Unit Off, Empty Box): High and Low Side
0 C / 32 F
1600 kPa, 16.0 bar, 232 psig
20 C / 68 F
1700 kPa, 17.0 bar, 2247 psig
38 C / 100 F
1800 kPa, 18.0 bar, 261 psig
-30 C (-22 F) Box, Unit Cooling:
High Side
2100 to 2300 kPa, 21.0 to 23.0 bar, 305 to 334 psig
Low Side
250 to 280 kPa, 2.5 to 2.8 bar, 36 to 41 psig
-60 C (-76 F) Box, Unit Cooling:
High Side
1400 to 1600 kPa, 14.0 to 16.0 bar, 203 to 232 psig
Low Side
900 to 1100 kPa, 0.9 to 1.1 bar, 131 to 160 psig
High Pressure Cutout Switch
Cutout
3250 ± 50 kPa, 32.5 ± 0.50 bar, 470 ± 7 psig
Cutin
2590 ± 250 kPa, 25.90 ± 2.5 bar, 375 ± 38 psig
High Pressure Relief Valve
Relief Pressure
3447 +520/-104 kPa, 34.47 +5.20/-1.04 bar, 500 +75/-15
psig
Reset
2758 kPa, 27.58 bar, 400 psig
Low Pressure Cutout Switch (MPC2000ID Units
Only)
Cutout
0 ± 20 kPa, 0.0 ± 0.2 bar, 6 in. vacuum to 3 psig
Cutin
70 ± 20 kPa, 0.7 ± 0.2 bar, 10 ± 3 psig
*When the compressor is removed from the unit, oil level should be noted or the oil removed from the compressor should be
measured so that the same amount of oil can be maintained in the replacement compressor.
**
Do
not
use or add standard synthetic or mineral oils to the refrigeration system. If Ester based oil becomes contaminated with
moisture or with standard oils, dispose of properly —
Do
not use!
Содержание Thermo King CRR DF MPC2000
Страница 5: ...4 ...
Страница 11: ...List of Figures 10 ...
Страница 13: ...Introduction 12 ...
Страница 19: ...Safety Precautions 18 ...
Страница 21: ...Service Guide 20 ...
Страница 47: ...Unit Description 46 ...
Страница 97: ...Microprocessor Controller 96 ...
Страница 101: ...Electrical Maintenance 100 ...
Страница 141: ...Structural Accessory Maintenance 140 ...
Страница 147: ...Refrigeration System Diagnosis 146 ...
Страница 149: ...Electrical Refrigeration and Controller Menu Flow Diagrams 148 This page intentionally left blank ...
Страница 150: ...149 CRR DF MPC2000 Controller Diagram ...
Страница 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Страница 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Страница 153: ...152 CRR DF MP3000A Controller Diagram ...
Страница 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Страница 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Страница 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Страница 159: ...158 CRR DF Off Cycle Standby Flow and Pressure Diagram Page 2 of 2 CRR DF Off Cycle Standby Flow and Pressure Diagram ...
Страница 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Страница 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...