Refrigeration Maintenance and Service Operations
117
6. Close the service valve on the R-23 recovery bottle.
7. Backseat the discharge service valve. Disconnect the refrigerant hose from the discharge valve.
8. With system pressures below 100 kPa, 1.00 bar, 15 psig, the R-23 system components can be
serviced.
If necessary, set a recovery machine for vapor recovery. Connect the recovery machine to a separate,
empty recovery bottle. Keep unit OFF and mid-seat the discharge service valve. Turn ON the recovery
machine and open the service valve on the recovery machine. Operate the recovery machine until system
pressures drop to 0 kPa, 0 bar, 0 psig pressure.
R-134a Vapor Recovery
1. Install a gauge manifold set on the R-134a refrigeration system. Attach the service line to the recovery
machine and properly purge the lines. Set the recovery machine for vapor recovery.
2. Keep unit OFF and mid-seat the discharge service valve.
3. Turn ON the recovery machine and open (back seat) both gauge manifold and hand valves.
4. Continue to operate the recovery machine until system pressures drop to 0 kPa, 0 bar, 0 psig pressure.
R-134a Liquid Recovery
1. Install a gauge manifold’s low-pressure line to the Schrader suction service valve on the suction
service valve of the R-134a compressor. Attach the manifold’s high-pressure line to R-134a receiver
tank service valve port. Attach the service line to the recovery machine and purge the lines.
2. Set recovery machine for liquid recovery and turn it ON.
3. Open (back seat) high-pressure valve on gauge manifold.
4. Operate the recovery machine until the unit system pressures reach approximately 0 kPa, 0 bar, 0 psig.
Evacuation and Cleanup of the Refrigeration System
Contamination
Whenever contaminants have entered the system, a thorough clean up is required to prevent damage or
loss of compressor.
It is well known by the refrigeration service industry that the purpose of evacuation is to remove moisture
and air from the refrigeration system before charging with new refrigerant after a system has been
opened. The importance of thorough evacuation and system preparation cannot be over emphasized.
Even infinitesimal quantities of air or moisture in a system can cause severe problems.
We know that the presence of moisture, oxygen, and heat under certain conditions can result in many
forms of damage. Corrosion, sludge, copper plating, oil breakdown, carbon formation, and eventual
compressor failure can be caused by these contaminants.
Things that will contaminate a system are (in order of importance):
•
AIR — with oxygen as a contaminant. Oxygen in the air reacts with the oil. The oil begins to break
down and can eventually lead to carbonization in the compressor and acid buildup. The longer this
breakdown process goes on, the darker the compressor oil becomes until finally the color is BLACK
indicating major system contamination.
Содержание Thermo King CRR DF MPC2000
Страница 5: ...4 ...
Страница 11: ...List of Figures 10 ...
Страница 13: ...Introduction 12 ...
Страница 19: ...Safety Precautions 18 ...
Страница 21: ...Service Guide 20 ...
Страница 47: ...Unit Description 46 ...
Страница 97: ...Microprocessor Controller 96 ...
Страница 101: ...Electrical Maintenance 100 ...
Страница 141: ...Structural Accessory Maintenance 140 ...
Страница 147: ...Refrigeration System Diagnosis 146 ...
Страница 149: ...Electrical Refrigeration and Controller Menu Flow Diagrams 148 This page intentionally left blank ...
Страница 150: ...149 CRR DF MPC2000 Controller Diagram ...
Страница 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Страница 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Страница 153: ...152 CRR DF MP3000A Controller Diagram ...
Страница 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Страница 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Страница 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Страница 159: ...158 CRR DF Off Cycle Standby Flow and Pressure Diagram Page 2 of 2 CRR DF Off Cycle Standby Flow and Pressure Diagram ...
Страница 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Страница 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...