FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
12 Cable Routing
Issue 01 (2019-03-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
180
Figure 12-15
Cable routes for the aisle lighting system
(1) AC actuator
(2) Light
(3) Light button
After aisle lights are installed, connect cables by performing the following steps:
Interconnect the male and female connectors of lights in the same group.
For lights in the same group, only the light in either end needs to be connected to the
power supply.
For lights in different groups, power must be supplied to each group separately.
Figure 12-16
Cable connections to lights in the same group
(1) AC actuator
(2) Light