FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
1 Installation Preparations
Issue 01 (2019-03-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4
Check Item
Requirement
Check Result
Power supply
380–415 V AC, 3-phase, 50/60 Hz
□ Compliant □
Incompliant
Fire extinguishing
Indoor gaseous fire extinguisher
□ Compliant □
Incompliant
Floor drain
DN50 or larger, made of cast iron or
stainless steel
□ Compliant □
Incompliant
Module grounding
The equipment room grounding
system must be a TN-S or TN-C-S
system
The equipment room ground grid
must have a ground resistance of 10
ohms at most (If the ground
resistance exceeds 10 ohms, ensure
that the equivalent ground radius of
the ground grid exceeds 5 m.)
Ground bars must be deployed over
the cable tray or under the raised
floor
□ Compliant □
Incompliant
Monitoring port
One LAN switch Ethernet port:
connects to the customer subnet to
monitor devices inside the module.
(Optional) Two fire control dry
contacts (access actuator and PDC
fire control terminal): connect to the
fire extinguishing system of the
equipment room for interaction.
SIM card: supports 3G (WCDMA)
communication and is compatible
with 2G (GSM) communication. At
least one SIM card is available.
NOTE
The prerequisite for using a SIM card is that
the site has signal coverage.
IP address: At least one IP address
for the ECC collector, the camera,
and the VCN respectively.
NOTE
An IP address is required for each camera.
□ Compliant □
Incompliant
If any of the requirements is not met, contact Huawei technical support.