FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
4 Hardware Installation Preparations
Issue 01 (2019-03-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
38
Category Name
Specifications
Remarks
The thickness of thermal
insulation foam wrapping main
chilled water supply and return
pipes (DN80): ≥ 40 mm.
Glue for
wrapping
pipes with
thermal
insulation
foam
Armaflex 820
Engineering
purchasing
Black rubber
adhesive with
thermal
insulation
foam
Recommended thickness > 3 mm
Engineering
purchasing
Joint sealant
The specifications of the sealant or
seal tape for screw threads are as
follows:
Applicable to all pipe materials
Anaerobic metal pipe thread
sealant with PTEF as the
padding
Glycol solution resistant, fit for
threads and pipes
Maximum gap: 0.5 mm
Pressure resistance: above 3
MPa
Compliant with the industry
standard JB/T7311-2008
Technical Specification for the
Application of Anaerobic Glue in
Engineering Machinery
Engineering
purchasing
Flange and
sealing gasket
DN80
Engineering
purchasing
Butterfly
valve
DN80, pressure resistance: 2.0 MPa
or more
Engineering
purchasing
Copper gate
valve
DN25, each for main chilled water
supply and return pipes, pressure
resistance: 2.0 MPa or more
Engineering
purchasing
Y-shaped
strainer
Recommended: pressure resistance
of 2.0 MPa or more, 20 filtration
pores, installed on the main chilled
water supply pipe
Engineering
purchasing, based on
pipes reserved onsite
Water
pressure
N/A
Engineering
purchasing, based on