FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
12 Cable Routing
Issue 01 (2019-03-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
176
Ensure that strong-current cables and weak-current cables are at least 100 mm away from
each other.
Connect the power cables from the general input unit side to the smart module.
Figure 12-10
Routing power cables and signal cables
(1) General input unit
(2) Power distribution unit
(3) Conversion unit
(4) Signal cable
(5) Network cabinet
(6) Power cable