FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
9 Installing Monitoring Devices
Issue 01 (2019-03-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
160
(4) Conversion cable end B,
connected to the water detection
cable
(5) Water detection cable end A,
connected to the conversion cable
(6) Water
detection cable
Procedure
Step 1
Connect the water detection cable to the conversion cable, as shown in
Figure 9-68
Connecting cables
(1) Conversion cable end B, connected to
the water detection cable
(2) Water detection cable end A, connected
to the conversion cable
The water detection cable and conversion cable are interconnected through the male and female
connectors.
Step 2
Connect the other end of the conversion cable to the water detector, as shown in
Figure 9-69
Connecting the water detector
----End