FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
12 Cable Routing
Issue 01 (2019-03-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
186
Figure 12-22
Base grounding diagram
(1) Base ground points
Connect one end of the base ground cable to any of the base ground points shown by (1)
in
, and connect the other end to the general ground copper bar of the
equipment room.
Connect one end of the base ground cable to any of the base ground points shown by (1)
in
, and connect the other end to the ground copper bar at the rear door
bottom inside the cabinet, as shown in
. Then connect the module ground
cables by following instructions in
Figure 12-23
Connecting the ground cable between the base and cabinet