9 Installing Monitoring Devices
Issue 01 (2019-03-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
156
Procedure
Step 1
Mark management areas based on the air conditioner layout.
Scenario 1: There is an odd number of IT cabinets between air conditioners. In this
scenario, categorize the cabinet in the middle of the two air conditioners to the area of
the air conditioner on the left (front view), as shown in
Components in the background with the same color belong to the same area.
Figure 9-62
Categorizing an odd number of cabinets
Scenario 2: There is an even number of IT cabinets between air conditioners. In this
scenario, categorize the cabinets evenly, as shown in
Components in the background with the same color belong to the same area.
Figure 9-63
Categorizing an even number of cabinets
Step 2
Assign T/H sensors by area.
Assign three T/H sensors to each area as follows:
1.
Assign the first T/H sensor to the cabinet furthest from the air conditioner, as shown by
(1) in
and
If there is the same number of cabinets on the two sides of an air conditioner (as shown by air
conditioner 3 in
and
), preferentially deploy a T/H sensor to the cabinet on the
left side of the air conditioner.
2.
Assign the second T/H sensor to the cabinet furthest from the other side of the air
conditioner, as shown by (2) in
and
3.
Assign the third T/H sensor to the cabinet that is between the first T/H sensor and the air
conditioner and near the air conditioner, as shown by (3) in
and