Maintenance and Inspection
Daily and Yearly Inspection Chart
Item Inspected
Check for…
Inspection
Cycle
Inspection
Method
Criteria
Daily Year
Overall
Ambient
environment
Extreme
temperatures &
humidity
9
Thermometer,
hygrometer
Ambient temperature
between –10 to 50
°
C,
Humidity 90% or less
non-condensing
Major
devices
Abnormal noise &
vib.
9
Visual and aural
Stable environment for
electronic controls
Power
supply
voltage
Voltage tolerance
9
Digital volt meter,
measure between
inverter terminals
[L1], [L2], [L3]
200V class: 50/60 Hz
200 to 240V (-15/+10%)
400V class: 50/60 Hz
380 to 460V (-15/+10%)
Main
circuit
Ground
Insulation
Adequate
resistance
9
Refer to P6-16
5 M
Ω
or greater
Mounting
No loose screws
9
Torque wrench
M3.5: 1.0Nm
M4: 1.4Nm
M5: 3.0
M6: 3.9 to 5.1Nm
M8: 5.9 to 8.8Nm
Components Overheating
9
Thermal trip
events
No trip events
IGBT Resistance
value
9
Refer to P6-17
Terminal
block
Secure connections
9
Visual No
abnormalities
Smoothing
capacitors
Leaking, swelling
9
Visual No
abnormalities
Relay(s) Chattering
9
Aural
Single click when
switching ON or OFF
Resistors Cracks
or
discoloring
9
Visual
Check Ohms of optional
braking res.
Control
circuit
Function Voltage
balance
between phases
9
Measure voltage
between U,V,W
Difference must be 2%
or less.
Protection circuit
9
e.g. Input Ex.trip
signal and check
inverter behavior
and alarm signal.
Functions properly.
Overall No
odor,
discoloring,
corrosion
9
Visual No
abnormalities
Capacitor Leaking,
swelling
9
Visual Undistorted appearance
Cooling
Cooling fan Noise
9
Power down,
manually rotate
Rotation must be
smooth
Dust
9
Visual
Vacuum to clean
Mounting
9
Visual Mounted
firmly
Heat sink
Dust
9
Visual
Vacuum to clean
Display LEDs Legibility
Visual
All LED segments work
Note 1:
The life of a capacitor is affected by the ambient temperature. See page 6–21.
Note 2:
Designed life of a cooling fan is.10 years. However, it is affected by the ambient
temperature and other environmental conditions.
Note 3:
The inverter must be cleaned periodically. If dust accumulates on the fan and
heat sink, it can cause overheating of the inverter.
Содержание WJ200 Series Software
Страница 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Страница 59: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Страница 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Страница 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Страница 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...
Страница 382: ...C 1 Drive Parameter Setting Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...