51
Using Intelligent Output Terminals
The intelligent output terminals are programmable in a similar way to the intelligent
input terminals. The inverter has several output functions that you can assign
individually to two physical logic outputs. One of the outputs is an open-collector
transistor, and the other output is the alarm relay (form C – normally open and
normally closed contacts). The relay is assigned the alarm function by default, but you
can assign it to any of the functions that the open-collector output uses.
Sinking Outputs, Open Collector
The open-collector transistor
output can handle up to 50mA. We
highly recommend that you use an
external power source as shown at
the right. It must be capable of
providing at least 50mA to drive
the output at full load. To drive
loads that require more than
50mA, use external relay circuits
as shown below right.
Sinking Outputs, Open Collector
If you need output current greater
than 50mA, use the inverter output
to drive a small relay. Be sure to
use a diode across the coil of the
relay as shown (reverse-biased) in
order to suppress the turn-off spike,
or use a solid-state relay.
CM2
-
+
11
Load
WJ200 Inverter
Logic output
common
12
CM2
-
+
11
WJ200 Inverter
Logic output
common
RY
12
Содержание WJ200 Series Software
Страница 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Страница 59: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Страница 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Страница 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Страница 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...
Страница 382: ...C 1 Drive Parameter Setting Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...