C
−
15
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Lnitial data Units
B050
Controlled deceleration on
power loss
Four option codes:
00
…
Trips
01
…
Decelerates to a stop
02
…
Decelerates to a stop with DC
bus voltage controlled
03
…
Decelerates to a stop with DC
bus voltage controlled, then
restart
U
00
−
B051
DC bus voltage trigger level
of ctrl. decel.
Setting of DC bus voltage to start
controlled decel. operation. Range
is 0.0 to 1000.0
U
220.0/
440.0
V
B052
Over-voltage threshold of
ctrl. decel.
Setting the OV-LAD stop level of
controlled decel. operation. Range
is 0.0 to 1000.0
U
360.0/
720.0
V
B053
Deceleration time of ctrl.
decel.
Range is 0.01 to 3600.0
U
1.0 sec
B054
Initial freq. drop of ctrl.
decel.
Setting of initial freq. drop.
Range is 0.0 to 10.0 Hz
U
0.0 Hz
B060
Maximum-limit level of
window comparator (O)
Set range, {Min.-limit level (
b061
)
+ hysteresis width (
b062
)x2} to
100 %
(Minimum of 0%)
U
100. %
B061
Minimum-limit level of
window comparator (O)
Set range, 0 to {Max.-limit level
(
b060
) - hysteresis width
(
b062
)x2} % (Maximum of 0%)
9
0. %
B062
Hysteresis width of window
comparator (O)
Set range, 0 to {Max.-limit level
(
b060
) - Min.-limit level (
b061
)}/2 %
(Maximum of 10%)
9
0. %
B063
Maximum-limit level of
window comparator (OI)
Set range, {Min.-limit level (
b064
+
hysteresis width (
b065
)x2} to
100 %
(Minimum of 0%)
9
100. %
B064
Minimum-limit level of
window comparator (OI)
Set range, 0 to {Max.-limit level
(
b063
) - hysteresis width
(
b065
)x2} % (Maximum of 0%)
9
0. %
b065
Hysteresis width of window
comparator (OI)
Set range, 0 to {Max.-limit level
(
b063
) - Min.-limit level (
b064
)}/2 %
(Maximum of 10%)
9
0. %
b070
Operation level at O
disconnection
Set range, 0 to 100%, or “no”
(ignore)
U
no -
b071
Operation level at OI
disconnection
Set range, 0 to 100%, or “no”
(ignore)
U
no -
b075
Ambient temperature setting Set range is,
-10~50
°
C
9
40
°
C
B078
Watt-hour clearance
Two option codes:
00
…
OFF
01
…
ON (press STR then clear)
9
00 -
b079
Watt-hour display gain
Set range is,
1.~1000.
9
1.
B082
Start frequency
Sets the starting frequency for the
inverter output, range is 0.10 to
9.99 Hz
U
0.50 Hz
B083
Carrier frequency
Sets the PWM carrier (internal
switching frequency), range is 2.0
to 15.0 kHz
U
2.0 kHz
Содержание WJ200 Series Software
Страница 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Страница 59: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Страница 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Страница 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Страница 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...
Страница 382: ...C 1 Drive Parameter Setting Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...