Low Load Detection Parameters
The following parameters work in
conjunction with the intelligent output
function, when configured. The output
mode parameter (
C038
) sets the mode of
the detection at which the low load
detection signal [LOC] turns ON. Three
kinds of modes can be selected. The
detection level parameter (
C039
) is to set
the level of the low load.
This function is for generating an early
warning logic output, without causing
either a trip event or a restriction of the
motor current (those effects are available
on other functions).
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Lnitial data
Units
C038
Output mode of low
current detection
Two option codes:
00
…
During acceleration,
deceleration and constant speed
01
…
During constant speed only
U
01
−
C039
Low current detection
level
Set the level of low load detection,
range is 0.0 to 2.0*inverter rated
current
U
INV rated
current
A
C039
Output
current
[LOC]
output
0
1
0
t
t
ON
Содержание WJ200 Series Software
Страница 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Страница 59: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Страница 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Страница 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Страница 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...
Страница 382: ...C 1 Drive Parameter Setting Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...