6
−
14
Restoring Factory Default Settings
You can restore all inverter parameters to the original factory (default) settings
according to area of use. After initializing the inverter, use the powerup test in Chapter
2 to get the motor running again. If operation mode (std. or high frequency) mode is
changed, inverter must be initialized to activate new mode. To initialize the inverter,
follow the steps below.
(1) Select initialization mode in
b084
.
(2) If
b084
=
02
,
03
or
04
, select initialization target data in
b094
.
(3) If
b084
=
02
,
03
or
04
, select country code in
b085
.
(4) Set
01
in
b180
.
(5) The following display appears for a few seconds, and initialization is completed with
d001
displayed.
Display during initialization
Initialization of trip history
5 HC
Initialization
mode
Initialization for area A
5 00
Initialization for area B
5 01
The left digit rotates during initialization
d001
Blinking alternately
HD mode
1-C
Operation
mode after
initialization
ND mode
1-v
High frequency mode
H-1
“B” Function
Func.
Code
Name
Description
B084
Initialization mode
(parameters or trip
history)
Select initialized data, five option codes:
00
…
Initialization disabled
01
…
Clears Trip history
02
…
Initializes all Parameters
03
…
Clears Trip history and initializes all parameters
04
…
Clears Trip history and initializes all parameters and EzSQ
program
b094
Initialization target
data setting
Select initialized parameters, four option codes:
00
…
All parameters
01
…
All parameters except in/output terminals and communication.
02
…
Only registered parameters in
U
xxx
.
03
…
All parameters except registered parameters in
U
xxx
and
b037
.
B085
Initial value select
Select default parameter values:
00
…
area A
01
…
area B
b180
Initialization trigger
This is to perform initialization by parameter input with
b084
,
b085
and
b094
. Two option codes:
00
…
Initialization disable
01
…
Perform initialization
Data of b084 is not saved in EEPROM to avoid unintentional initializing.
Содержание WJ200 Series Software
Страница 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Страница 59: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Страница 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Страница 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Страница 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...
Страница 382: ...C 1 Drive Parameter Setting Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...