4
−
54
Run Signal
When the [RUN] signal is selected as an
intelligent output terminal, the inverter
outputs a signal on that terminal when it is
in Run Mode. The output logic is active low,
and is the open collector type (switch to
ground).
Option
Code
Terminal
Symbol
Function Name
State
Description
00
RUN
Run Signal
ON
when inverter is in Run Mode
OFF
when inverter is in Stop Mode
Valid for inputs:
11, 12, AL0 – AL2
Example for terminal [11] (default output
configuration shown – see
page 3-90
):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see
page 4-52 and 3-90
):
See I/O specs on
page 4-6
Required settings
(none)
Notes:
•
The inverter outputs the [RUN] signal whenever
the inverter output exceeds the start frequency
specified by parameter
B082
.
The start frequency
is the initial inverter output frequency when it turns
ON.
•
The example circuit for terminal [11] drives a relay
coil. Note the use of a diode to prevent the
negative going turn-off spike generated by the coil
from damaging the inverter’s output transistor.
RY
Inverter output
terminal circuit
CM2
11
RUN
AL1
Power
supply
Load
AL0
AL2
Inverter logic
circuit board
RUN
[FW,RV]
1
0
Output
frequency
t
Run
signal
1
0
start freq.
B082
ON
Содержание WJ200 Series Software
Страница 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Страница 59: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Страница 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Страница 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Страница 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...
Страница 382: ...C 1 Drive Parameter Setting Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...