“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Lnitial data
Units
A070
Acceleration hold time
Sets the duration of
acceleration hold, range is 0.0
to 60.0 seconds
U
0.0 sec.
A071
PID enable
Enables PID function,
three option codes:
00
…
PID Disable
01
…
PID Enable
02
…
PID Enable with reverse
output
U
00
−
A072
PID proportional gain
Proportional gain has a range
of 0.00 to 25.00
9
1.0
−
A073
PID integral time constant
Integral time constant has a
range of 0.0 to 3600 seconds
9
1.0 sec
A074
PID derivative time constant Derivative time constant has a
range of 0.0 to 100 seconds
9
0.00 sec
A075
PV scale conversion
Process Variable (PV), scale
factor (multiplier), range of 0.01
to 99.99
U
1.00
−
A076
PV source
Selects source of Process
Variable (PV), option codes:
00
…
[OI] terminal (current in)
01
…
[O] terminal (voltage in)
02
…
ModBus network
03
…
Pulse train input
10
…
Calculate function output
U
00
−
A077
Reverse PID action
Two option codes:
00
…
PID input = SP-PV
01
…
PID input = -(SP-PV)
U
00
−
A078
PID output limit
Sets the limit of PID output as
percent of full scale,
range is 0.0 to 100.0%
U
0.0 %
a079
PID feed forward selection
Selects source of feed forward
gain, option codes:
00
…
Disabled
01
…
[O] terminal (voltage in)
02
…
[OI] terminal (current in)
U
00
−
A081
AVR function select
Automatic (output) voltage
regulation, selects from three
type of AVR functions, three
option codes:
00
…
AVR enabled
01
…
AVR disabled
02
…
AVR enabled except during
deceleration
U
02
−
a281
AVR function select,
2
nd
motor
U
02
−
A082
AVR voltage select
200V class inverter settings:
……
200/215/220/230/240
400V class inverter settings:
……
380/400/415/440/460/480
U
200/
400
V
a282
AVR voltage select,
2
nd
motor
U
200/
400
V
a083
AVR filter time constant
Define the time constant of the
AVR filter, range is 0 to 10 sec.
U
0.300 sec
Содержание WJ200 Series Software
Страница 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Страница 59: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Страница 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Страница 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Страница 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...
Страница 382: ...C 1 Drive Parameter Setting Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...